LuminBlock H SeriesC&I All-in-one Hybrid ESS · 37.5–60 kW
C&I All-in-one Hybrid ESS · the paperwork

Certifications and Compliance

A certificate answers one question: which standard, tested by whom, at which version. A buyer needs three of those answers before the equipment crosses a border.

What is held, what a CB certificate does and does not mean, and which approvals sit outside the current set.

CB IEC 62619:2022 cells and batteriesCB IEC 63056 battery systemsCEI 0-21 Italy grid connectionIP55 enclosure, C4 standard
HELD

Three Certificates Are Held Today

C&I All-in-one Hybrid ESS holds CB certificates to IEC 62619:2022 and IEC 63056, plus the Italian CEI 0-21 grid code. Compliance reports cover IEC/EN 62477-1, the EN IEC 61000-6 series, IEC 61727, IEC 62116, EN 50549-1/-10, IEC 62109, IEC 60730 and UN38.3.

CertificateScopeMarket
CB IEC 62619:2022Safety of industrial lithium cells and batteriesIECEE member countries
CB IEC 63056Secondary cells and batteries for electrical energy storageIECEE member countries
CEI 0-21Grid connection of storage in low voltageItaly

Alongside these sit a CE declaration, RoHS and WEEE compliance, and a UN38.3 transport test report for both the pack and the finished cabinet.

CB SCOPE

A CB Certificate Is Not a Grid Approval

CB reports are issued under the IECEE scheme. They prove the product was tested to a standard by an accepted laboratory, and they let a national body convert the result into its own approval.

That conversion is separate work. Only Italy is covered by a grid-connection certificate in this set. For other countries the local body, the utility or the installer handles the filing, and we supply the reports they need.

Certificates also have versions. Ask the certification department for the certificate number and the revision that is valid on the day your equipment ships.

REPORTS

The Test Reports Behind the Certificate

The cabinet is tested to IEC/EN 62477-1 for power electronic converter safety, IEC/EN 62109-1 and -2 for the inverter, and EN IEC 61000-6-1 through -4 for electromagnetic compatibility.

Grid behaviour is covered by EN 50549-1 and -10, IEC 61727 and IEC 62116. Additional reports cover IEC/EN 62920, IEC 60730 and the transport test UN38.3.

SAFETY

Safety Is Built in Layers

Three passive layers contain a fault: cell chemistry, pack structure and enclosure. Four active systems respond to it: aerosol fire suppression, smoke, temperature and water sensors, plus an emergency stop.

AFCI is standard, and string-level shutdown isolates a PV string without taking the whole array down. Those two features are the ones insurers ask about first.

CORROSION

Distance to the Sea Sets the Class

Ten kilometres or more from the coast, C3 applies. Between one and ten kilometres, C4 is the standard finish. Within a kilometre, C5 or C5-M is needed and must be written into the contract.

The default cabinet is C4 in IP55. Coastal sites are quoted with the higher class rather than corrected on site.

FAQ

Questions about certifications and compliance

Can you supply certificates for my market?

For Italy, yes. Elsewhere we supply the CB reports and the test data your local body or utility asks for.

Which version of IEC 62619 applies?

The 2022 edition, as stated on the CB certificate. Ask for the certificate number with the revision date.

Does IP55 cover outdoor installation?

IP55 covers dust and water jets. Coastal and flood-prone sites still need the corrosion class and the mounting height checked.

Get the Certificate Set for Your Market

Name the country and the utility. The reply lists which documents already exist and which filing the local body still has to do.